The Online Residual Chlorine Monitor by Daruifuno delivers real-time, precise chlorine monitoring for dependable water quality control.Industrial Chlorine Controller for Accurate Monitoring in Water Treatment Facilities
| Model | ADS2-C3-A | ADS2-C3-D |
| Measuring Object | Residual chlorine | |
| Measuring Principle | membrane-covered, amperometric system | |
| Sensor Input | Compatible with all DRFN 4-20mA Version Chlorine Sensors | |
| Measuring Range | Max. 0.005~200ppm, related to sensors | |
| Resolution | Min. 0.001ppm, related to sensors | |
| Temp. Compensation | Automatic compensation | |
| Calibration Method | DPD comparison method, 1~2 points or more | |
| Relay Control | Two settable SPST relays, Max. load of 3A/250VAC | |
| Current Output | A settable 0/4~20mA current, Max. load 1000Ω | |
| Digital Output | 2-wire RS485 interface, MODBUS RTU, support JSON | |
| Display Screen | 3.2-inch black and white graphic LCD display, pixel 128*64 dot matrix LCD | |
| Configuration | Power off protection, parameters are retained indefinitely | |
| Time or Data | Display Year/month/day, hour/min/second, record 10000 historical data | |
| Maintenance Record | Record the last 100 calibration maintenance data, MCU over temperature alarm log | |
| Language | English and Chinese | |
| Protection Grade | IP66 | |
| Work Temperature | 0~60ºC,RH<95% ( no condensation) | |
| Storage Temperature | -20~70ºC,RH<55% ( no condensation, precision instruments) | |
| Enclosure Material | Enhanced ABS | |
| Dimension | 144*144*120 mm (hole size 138*138 mm) | |
| Installation | Wall mounting, pipe clamping, panel installation | |
| Electrical Interface | Reserve three M12*1.5 gland heads, the wire diameter is 3~6.5mm | |
| Power Supply | AC: 100~240V 50/60Hz | DC: 18~36V |
| Power Consumption | About 7W | |
| Weight | 1600g | |